IA-DJYPVP 300/500V Intrinsic-Safety Shielded Instrument Cable

IA prefix on the model code designates the cable as suitable for intrinsic-safety loops in hazardous areas — refineries, LNG terminals, paint plants. Light-blue outer sheath visually distinguishes IS cable from standard process instrumentation so the two cannot be confused at termination.
Technical Specifications
| Conductor | Annealed copper, Class 2 stranded |
| Insulation | PE |
| Pair shielding | Aluminum-mylar foil + drain wire |
| Overall shielding | Aluminum-mylar foil + drain wire |
| Outer sheath | Light-blue PVC (IS-color) |
| Hazardous-area rating | Suitable for Zone 0 / 1 / 2 IS loops |
| Pair counts | 1 / 2 / 4 / 7 / 8 / 12 / 16 pairs |
| Conductor size | 0.5 – 2.5 mm² |
| Operating temperature | 70 °C |
| Compliance | IEC 60079-14 wiring rules |
Compliance Standards
- ✓IEC 60079-14
- ✓GB/T 9330.3
- ✓GB 50058 (Hazardous area)
Overview
Same conductor + pair construction as ZC-DJYPVP, but with: light-blue outer sheath (per IEC 60079 hazardous-area cable color convention), tighter geometric tolerances to limit pair-to-pair capacitance, individual + overall shielding to minimize cross-talk between IS and non-IS pairs. Suitable for Zone 0 / Zone 1 / Zone 2 explosion-risk areas per IEC 60079-14 wiring rules.
Key Features
Light-blue IS color
Visually unmistakable from standard instrument cable — eliminates IS/non-IS terminal mix-ups during commissioning.
Bounded capacitance and inductance
Geometric tolerances control L/C per IEC 60079-14 simple-apparatus wiring rules — IS-loop barrier calculations stay valid.
Applications
Petrochemical instrumentation
Refinery, LNG terminal, chemical plant IS loops where Zone 0/1 cable rules apply.