Power Cables · Low-Voltage Power Cables · 0.6/1kV

WDZN-YJY 0.6/1kV Copper XLPE LSZH Fire-Resistant Power Cable

WDZN-YJY 0.6/1kV fire-resistant copper power cable by Zhejiang Hongce

For circuits that must keep delivering current through a building fire — emergency lighting, smoke-extraction fans, fire pump motors, evacuation alarm panels — the cable construction adds a mica-glass tape barrier under the XLPE insulation. The cable continues to deliver rated power for 90 minutes in a 750°C flame test.

Conductor materialAnnealed copper, Class 2 stranded
Fire-resistant layerMica-glass tape, two layers
InsulationXLPE
Outer sheathHalogen-free flame-retardant polyolefin
Fire-resistance testIEC 60331-21 (830°C × 90 min, voltage withstood)
Flame propagationIEC 60332-3-22 Category B
Smoke densityIEC 61034 — low
Halogen contentIEC 60754 — zero
Rated voltage U₀/U0.6/1 kV
Cross-sections available1.5 – 400 mm²
  • IEC 60502-1
  • IEC 60331-21 (Fire resistance)
  • IEC 60332-3-22 Category B
  • GB/T 19666 (FR-classified cable)
  • BS 6387 CWZ (on specific cross-sections, by request)

Overview

Conductor wrapped in two layers of mica-glass tape, then XLPE insulation, then halogen-free flame-retardant outer sheath. The mica layer is the circuit-integrity element: it withstands fire temperatures that would degrade XLPE alone. Verified to IEC 60331-21 (830°C × 90min) — the standard cited in SEA hospital, transit, and high-rise fire codes for life-safety circuit integrity.

Key Features

01

90 minutes circuit integrity at 830°C

IEC 60331-21 verified — the standard SEA hospital, metro, and high-rise codes cite for life-safety power circuits.

02

Triple safety properties

Fire-resistant + flame-retardant + halogen-free + low-smoke in one cable — no need to bundle four products for one project.

Applications

Hospital life-safety circuits

ICU emergency power, theatre lighting, fire pump motors, smoke-extraction fans.

Tunnel and metro emergency systems

Emergency lighting, evacuation alarm power, jet-fan motor feeds.