Power Cables · Medium-Voltage Power Cables · 8.7/15KV

YJV 8.7/15 kV Copper Conductor XLPE Insulated PVC Sheathed Medium Voltage Power Cable

YJV 8.7/15 kV three-core power cable cutaway showing copper conductors, XLPE insulation, copper tape screens and PVC sheath

YJV 8.7/15 kV is an unarmoured medium voltage power cable with copper conductors, XLPE insulation and a PVC sheath. Designed for fixed power distribution in industrial plants, substations and infrastructure projects, it suits cable ducts, tunnels and other protected routes. Specify core configuration, conductor size, screen requirements and order quantity to request a quotation matched to your project.

Rated VoltageU₀/U: 8.7/15 kV; Maximum System Voltage (Um): 17.5 kV
Conductor MaterialCopper Conductor
Conductor ClassClass 2 Stranded Conductor
Insulation SystemXLPE (Cross-linked Polyethylene) Insulation
Outer SheathPVC (Polyvinyl Chloride) Sheath
Flame PerformanceFlame-retardant Performance, if Specified, Subject to the Declared Grade and Supporting Test Report
Cable StructureCopper Conductor + Semi-conductive Conductor Screen + XLPE Insulation + Semi-conductive Insulation Screen + Copper Tape Screen + Fillers and Binding for Three-core Construction + PVC Outer Sheath; Unarmoured
Standard ComplianceGB/T 12706.2-2020; IEC 60502-2; GB/T 3956 / IEC 60228 for Conductors. Compliance Subject to Manufacturer Documentation
Operating Temperature90°C Maximum Continuous Conductor Temperature
Short Circuit Temperature250°C Maximum Conductor Temperature, for a Maximum Duration of 5 Seconds
Available SizesThree-core, Following the Template; Available Conductor Cross-sectional Areas to Be Confirmed by the Manufacturer
Installation MethodFixed Installation in Ducts, Tunnels and Cable Trenches; Direct Burial Where Permitted by the Cable Design and Site Conditions, with Appropriate Mechanical Protection
  • ✓GB/T 12706.2-2020
  • ✓IEC 60502-2
  • ✓ GB/T 3956
  • ✓IEC 60228

Overview

YJV 8.7/15 kV XLPE power cable is designed for fixed medium voltage power distribution in industrial plants, substations and commercial infrastructure. Combining copper conductors, cross-linked polyethylene insulation and a PVC outer sheath, it provides a practical cable option for projects requiring an unarmoured construction. The rated voltage designation, U₀/U, is 8.7/15 kV. The copper conductor carries electrical current, while XLPE insulation provides the main dielectric layer. Medium voltage cable construction also incorporates conductor and insulation screens, together with a metallic screen. The PVC outer sheath covers and protects the underlying cable components. The detailed screen design, conductor construction and cable dimensions should be defined in the approved technical specification, allowing buyers to compare offers on a consistent basis. Typical applications include distribution feeders within industrial facilities, connections between substations and distribution equipment, and other permanent medium voltage circuits. YJV cable can be considered for cable ducts, tunnels and appropriately protected cable routes. Selection depends on the installation environment, mechanical protection and the electrical requirements of the network. For engineering and procurement teams, cable selection starts with the core configuration and conductor cross-section. Current-carrying capacity, voltage drop and short-circuit requirements must be assessed against the actual installation conditions. Ambient temperature, cable grouping and installation method all influence the final selection. Cable dimensions and screen requirements also help determine compatibility with joints and terminations. For a comparable quotation, provide your cable schedule, required lengths, total quantity, installation method and destination. Include the applicable manufacturing standard, screen specification, sheath requirements and any project inspection requirements. Agree on the technical datasheet, compliance documentation and required test reports before placing the order. Specifying drum lengths, cable marking and packing requirements at the enquiry stage also helps align delivery with site installation plans. Whether sourcing for a new distribution project or replacing an existing feeder, a clearly specified YJV 8.7/15 kV cable makes technical evaluation and purchasing more straightforward. Send your project requirements to request a quotation aligned with your approved cable specification.

Key Features

01

8.7/15 kV Rated Voltage

Rated U₀/U of 8.7/15 kV for fixed medium voltage power distribution.

02

Copper Conductors

High-conductivity copper provides low electrical resistance for efficient power transmission.

03

XLPE Insulation

Cross-linked polyethylene insulation delivers electrical insulation and heat resistance.

04

Screened Construction

Conductor and insulation screens help control electrical stress within the cable.

05

PVC Outer Sheath

Protects internal cable layers against abrasion during handling and installation.

06

Unarmoured Design

Suitable for ducts, tunnels and cable routes with appropriate mechanical protection.

Applications

YJV 8.7/15 kV power cables installed in protective underground ducts for urban distribution

Urban Underground Distribution

Medium voltage distribution through protected underground ducts for urban infrastructure.

YJV 8.7/15 kV power cables routed on cable trays to industrial plant switchgear

Industrial Plant Power Supply

Fixed medium voltage feeders supplying factory substations and plant distribution systems.

YJV 8.7/15 kV power cables connecting a substation transformer through a cable trench

Substation Feeder Connections

Medium voltage cable connections between transformers, switchgear and outgoing feeders.

YJV 8.7/15 kV power cables secured on support racks inside an underground utility tunnel

Underground Cable Tunnels

Supported cable routes in dry utility tunnels for accessible power distribution.